The FG-SYS digital unit is designed to be used with TTK digital sense cables for water, bases and acid leak detection.
In the event of a fault on the sense cables (leak or cable break):
Primary responses from the FG-SYS unit:
- An audible alarm is triggered, the indicator light changes from green to red and a relay is activated.
- The display on the panel shows the leak location (to the nearest 1 metre) and fault’s details (type of fault, leak or cable break), with time and date.
Second
FG-SYS
FEATURES
- Wall mounted.
- 3 outputs are available, can be used independently.
- Up to 120 lengths of sense cables can be managed independently by the unit.
- 30 events history log allows to track leaks and cable breaks.
- 2 interface types for connection to building management and process control systems:
- Two independent serial interfaces, each of them can be set for
RS232 or RS422/485. - 9 relay contacts: 8 configurable relays + 1 specific relay for power interruption.
- 8 relay positions are defined by a LED indicator.
- Total programmable relays.
- Two independent serial interfaces, each of them can be set for
- Password is required for security.
BENEFITS
- Pin-point location of a leak (to 1 metre).
- Each sense cable is addressable and can be customized by assigning a specific identity and name.
- Multiple simultaneous leaks can be detected (120 cables = 120 alarms).
- Two different types of sense cables (for detecting water and acid liquids) can be connected on the same panel for a truly bespoke system.
- Cable break faults can be detected (to the nearest cable).
- When a cable break occurs, the system maintains its integrity and keeps monitoring all cables installed before that break.
- Compatible with existing monitoring systems (Trend BMS etc.)
- Extension and upgrade of the system is easy. No additional power source or zoning panels are required.
- Minimum maintenance required.
TECHNICAL DATA
Compatibility | Sense cables (digital): FG-EC, FG-AC Sense cables (analog through FG-DTCS box): FG-ECS, FG-ACS Diversion boxes: FG-DTC, FG-DTCS, FG-DCTL Accessories: TTK 8723 jumper cable, FG-CLC, FG-TMC |
Dimensions & Weights | W: 200mm H: 250mm D: 100mm Weight: 3kg |
Maximum Length of Sense Cable | 1800 meters (600 meters per circuit) |
Accuracy | +/- 1 meter |
Operating Languages | English, French, German |
Dimensions | 200x250x100mm (Wall mounted, F) |
Supply Voltage | 100-240VAC, 50/60Hz, 15W |
Working Temperature Range | 0°C to 50°C |
Working Humidity | 5% to 95% non-condensing |
Relay Types | Single contact NO-NC |
Alarm Relays | Eight programmable relays for leaks and/or breaks with status LED, plus one power fail relay |
Supported Protocol | Modbus RS232, RS422, RS485, available on two independent interfaces |
Maximum Switching Voltage | 125 V AC and 220 V DC |