The FG-STAD is designed to be used with the TTK FG-OD range of hydrocarbon leak detection sense cables, or the hydrocarbon point sensor, FG-ODP. It allows TTK sense cables or point sensors to function in a fully stand-alone mode, without fixed voltage power supply, thanks to its embedded battery. It also allows easy interfacing to third-party supervising equipment and is equipped with two unipolar outputs. One output reacts when the connected sense cable or point sensor detects a hydrocarb

FG-STAD

FEATURES

  • The FG-STAD unit monitors one hydrocarbon leak point sensor or one hydrocarbon sense cable.
  • No voltage supply is needed, the panel is supplied with an embedded battery with a lifespan of at least three years.
  • Accessible terminals for quick installation.
  • Two discreet unipolar outputs which provide easy interfacing to third-party supervising equipment.
  • External alarm device: flashing light, buzzer, horn, …

BENEFITS

  • The FG-STAD is simple to use and install, and is ideal for a small or/and remote application for hydrocarbon leak detection.
  • Minimal maintenance, with a periodical battery change every three years being all that is required.

TECHNICAL DATA

Compatibility Hydrocarbon sense cables: FG-OD, FG-ODC, FG-ODR; Point Sensor: FG-ODP
Capacity Capacity limited to 1 detector, either a hydrocarbon point sensor or a hydrocarbon sense cable
Enclosure Type IP65 ; aluminum alloy
Glands Material Stainless steel
Operating Temperature -30°C to 80°C
Max. Switching Capacity 26VCC and 50mA
Supply Voltage No voltage supply
Dimensions (W,H,D) 115 x 90 x 55 mm