datatech, infra datatech indonesia, ttk, liquid leak detection
The Leading Digital Infrastructure Data Center
+628118201430
FG-ODC+ is a digital sense cable for detection and location, along the entire length, of liquid hydrocarbons and liquid insoluble in water and their vapors. It allows multiple leak detection and location thanks to independent digital addressing, enabled by an embedded microchip in each FG-ODC+ sense cable. The sensor element is optimized for very fast response with light to middle distillates, and is sensitive to heavy oils such as conventional crude oils, dilbit / synbit, as well as to

FG-ODC-Plus

FEATURES

  • Standard length (3 m) sensor sections or long line section allowing optimised system architecture.
  • Microcontroller embedded in each FG-ODC+ sense cable allowing independent digital transmission to the alarm unit.
  • Standard length sense cable provided with built-in plug-socket connector.
  • Structure of the sense cable comprising a silicon sensing wire, a continuity wire, a communication wire (proprietary bus) and the power supply wires. Protective external PE braid built on the cable.
  • Intrinsically safe - can be used in classified areas: Ex ia IIB T4 Ga (IECEx “Zone 0”).

BENEFITS

  • Reliable detection:
    • Sensitive to heavy oils and vapors.
    • Insensitive to water, inorganic pollutants and external loads (pressure).
  • High sensitivity: examples of detection time: Diesel at 3-5 minutes  (*), Gasoline: less than 1 minute (*).
  • Detects and locates hydrocarbon leaks on the section length.
  • The same unit FG-NET can be connected to FG-ODC+ sense cables and mixed with water or acids / bases sense cables at the same time.
  • Easy to install and remove: standard FG-ODC+ cables pre-connected with male / female connectors.

Note (*): depending on liquid composition and leak conditions

TECHNICAL DATA

Cable nominal diameter 10 mm
Connector nominal diameter 16 mm
Embedded (Long Line) connection nominal diameter 16 mm
Cable nominal weight (without connectors) 7 kg / 100 m
Min. bending radius 100 mm
Max. Pressure 3 bar
Min. Max. working temperature -30°C < Tamb < +100°C
Direct burial Possible
Maximum tensile strength (incl. connection) 40 kg
Expected life span (at working conditions) >10 years
Explosive area classification Ex ia IIB T4 Ga (ATEX “Zone 0”)
Connector protection index classification (DIN/EN/IEC60529) IP 68