+628118201430
The TTK Sense Cable FG-ECX detects the presence of conductive liquids at any point along its length. The FG-ECX sense cable can be connected to two kinds of TTK’s alarm units: Locating Alarm Unit and Non-locating Alarm Unit. It detects and locates leaks to the nearest metre when connected to the locating alarm unit. The Sense Cable FG-ECX is available in standard, pre-finished lengths of 3, 7 or 15 metres complete with connectors. Each FG-ECX sense cable is made with special Low Smoke Zero Hal

FG-ECX

A RELIABLE SENSE CABLE

The FG-ECX sense cable performs the following functions:

  • Rapidly detects the leak of any liquid along the length of the cable.
  • Detects and locates leaks to the nearest metre when connected to the locating units FG-ALS8 or FG-ALS4.
  • Detects leaks only when connected to the non-locating unit FG-A.
  • Detects any break or cut to the cable.

Non-absorbant design can be reset in seconds after removal of the leak.

Manufactured with the low smoke zero halogen (LSZH or LS0H) materials, FG-ECX cable emits, when burned, a less optically dense smoke that releases at a lower rate than a non-LSZH cable.

A MODULAR SYSTEM

The FG-ECX sense cable ensures permanent protection in areas at risk. FG-ECX is installed to provide the best possible protection in order to cover risks and limit the financial consequences of an undetected leak.

EASY INSTALLATION

The male and female connectors at the end of each length of FG-ECX cable give quick and dependable connection.

Fixing clips are used to fasten the sensing cables in the chosen areas.

A TOUGH AND STURDY DESIGN

Small in diameter, the FG-ECX sense cable is light, flexible and of an easily identifiable dark blue colour and yellow colour on male connector tip. Its helical jacket construction, compression connected on an extruded central core, reduces the risk of contamination and false alarms. It is made from the highest quality materials which are abrasive resistant in hostile environments.

TECHNICAL DATA

 
Compatibility Alarm units: FG-ALS8, FG-ALS4, FG-A
Max. Rated Temperature 85°C
Weight 25g per metre (without connector)
Sense Cable Diameter 7.5 mm with jacket (without connector)
Liquid Quantity to Active Alarm 50 - 100 mm on the sense cable
FG-ECX Colour Light blue