The FG-ALS Alarm Location System is designed to be used with TTK analog sense cables; FG-ECS, FG-ACS and FG-ECX, FG-ACX to give instant detection of liquid leaks (water, acid or base).
A LCD display and three LED’s on the front panel indicate presence of Power Supply (green), Leak Detected (red) or Cable Break (yellow). The FG-ALS also features an RS485MODBUS/JBUS serial link to integrate to a variety of intelligent monitoring systems.
If a leak is detected an audible alarm is triggered. The L
FG-ALS
FEATURES
- Available in an attractive wall mounted unit (FG-ALS).
- The unit can control sense cables up to 150 metres.
- Visual and Audible indicators for the type of fault (leak or cable break).
- Two zero volt contact relays provide numerous signalling and centralised monitoring options.
- RS485 serial link with MODBUS provides a variety of intelligent interfacing options.
BENEFITS
- Accurate reporting of leak location.
- Detects cable break faults.
- Compatible with existing monitoring systems.
- The FG-ALS unit is accurate and easy to use, ideal for small and medium applications where accurate leak location is required.
TECHNICAL DATA
Compatibility | Analog sense cables: FG-ECS, FG-ECX, FG-ACS, FG-ACX |
Enclosure TYpe | ABS material (rated to UL94HB) |
Operating Temperature | 0°C to 50°C |
Serial Interface Physical Support | Optoisolated two wire RS485 |
Serial Link Parameters | 9600 bauds, 8 data bits, 1 stop, no parity |
Supported Protocol | MODBUS, funcions 3 and 4 |
Relays Type: Leak + Cable Break | 1 SPOT single contact NO-NC |
Dry Relay Max. Switching Voltage | 125 VAC or 220 VDC |
Relay Max. Switching Capacity | 60W (30V x 2A) |
Power Consumption | 2 VA |
Supply Voltage | 230 VAC / 110 VAC - 50/60 Hz or 12-24VAC, 15-30 VDC |
Dimmension (W, H, D) | 172 x 86.6 x 55 mm |