The FG-A alarm unit is designed to be used with TTK analog sense cables; FG-ECS, FG-ECX, FG-ACS and FG-ACX, to give immediate detection of liquid leaks (water, acid or base).
LED’s on the front panel indicate presence of Power Supply (green), Leak Detected (red) or Cable Break (yellow).
Responses on the FG-A alarm unit:
- In the case of a leak an audible alarm is triggered. The red LED is switched on and the leak relay is activated.
- In the case of cable break an audible alarm is triggered,
FG-A
FEATURES
- Available in both wall mounted and rack mounted (19’’ and 2U).
- The unit can control sense cables up to 15 metres.
- Visual and audible indicators for both types of fault (leak or cable break).
- Flexible supply voltage: 12-24VAC ;15-30VDC or 100-240VAC 50/60Hz.
- Easily accessible terminals for rapid installation.
- Two zero volt contact relays provide numerous signalling and centralised monitoring options.
BENEFITS
- The FG-A is simple and easy to use, your ideal choice for smaller or
remote applications - A simple bi-annual test is all that is required.
TECHNICAL DATA
Compatibility | Analog sense cables: FG-ECS, FG-ECX, FG-ACS, FG-ACX |
Box Type |
Wall mounted: ABS flame retardant UL94V0 Rack mounted: Alumunium |
Operating Temperature | 0°C to 50°C |
Relays Type: Leak & Cable Break | Single contact No-NC |
Max. Relay Voltage | 125 VAC and 220 VDC |
Max. Relay Capacity | 60W (30V x 2A) |
Supply Voltage | 12-24 VAC; 15-30 VDC or 100 - 240 VAC 50/60 Hz |
Dimensions (W, H, D) | 165 x 85 x 55 mm and 482.60 x 88,10 mm |
Weight | 0.56 kg |