datatech, infra datatech indonesia, ttk, liquid leak detection
The Leading Digital Infrastructure Data Center
+628118201430
E2639-HFC is a halocarbon refrigerants detector designed for reliable gas leak monitoring in industrial and commercial environments. It detects a wide range of refrigerants such as R-22, R-134a, R-404a, R-410a, and new-generation low-GWP gases like R-1234yf. Equipped with dual analog outputs, RS485 Modbus RTU, relays, and optional WiFi configuration, the device ensures flexible integration into safety and automation systems. Its robust IP65 enclosure, long sensor lifetime, and advanced diagnosti

E2639-HFC

FEATURES

  • Two 4–20 mA user-configurable analog outputs
  • RS485 Modbus RTU digital interface
  • 3 × SPDT relays (2 alarm, 1 fault)
  • 2 × 24 V outputs for alarm signal control*
  • Magnetic button for alarm reset & WiFi activation
  • Optional WiFi interface for configuration and calibration
  • Heavy-duty IP65 protected ABS enclosure

BENEFITS

  • Wide refrigerant detection range, including HFCs and new low-GWP alternatives
  • High sensitivity with 1 ppm resolution
  • Reliable monitoring with self-diagnostics and startup functionality check
  • Long sensor lifetime (>5 years) with low maintenance interval (12 months)
  • Flexible integration with analog, digital, relay, and WiFi connectivity options
  • Easy installation with wall-mount ABS housing and cable glands
  • Suitable for industrial and commercial HVAC/refrigeration environments.

TECHNICAL DATA

Detected gases

R-22, R-134a, R-143, R-404a, R-407c, R-410a, R-449a, R-507, R-514a, R-1234ze, R-1233zd, R-1234yf, etc.

Default calibration

Methane (CH4)

Sensor type

Metal-oxide semiconductor

Sampling method

Diffusion

Detection range

0...1000 ppm / 0...2500 ppm

Resolution

1 ppm

Response time (T90):

< 120 s

Sensor lifetime

> 5 years

Signal update

Every 1 second

Digital interface

RS485 (Modbus RTU)

Enclosure

Grey ABS plastic, wall mount, IP65

Warm-up time

Warm-up time

Power supply

14–36 VDC (default), 24 VAC or 230 VAC optional